Harrogate power station

Harrogate power station supplied electricity to the town of Harrogate and the surrounding area from 1897 to 1960. The power station was built by the Harrogate Corporation which operated it until the nationalisation of the British electricity supply industry in 1948.

Harrogate power station
Map
CountryEngland
LocationHarrogate
Coordinates54°00′03″N 01°33′17″W / 54.00083°N 1.55472°W / 54.00083; -1.55472
StatusDecommissioned
Commission date1897
Decommission date1960
OwnersHarrogate Corporation (1897–1948), British Electricity Authority (1948–55), Central Electricity Authority (1955–57), Central Electricity Generating Board (1958–60)
OperatorsHarrogate Corporation (1897–1948), British Electricity Authority (1948–55), Central Electricity Authority (1955–57), Central Electricity Generating Board (1958–60)
Thermal power station
Primary fuelCoal
Secondary fuelDiesel oil
Turbine technologyReciprocating engines and steam turbines
Cooling sourceSpray cooling pond
Power generation
Nameplate capacity15.875 MW
Annual net output9501 MWh (1946)

History

edit

The Harrogate Corporation applied for a Provisional Order under the Electric Lighting Acts  to generate and supply electricity to the town of Harrogate. An Order was granted by the Board of Trade and was confirmed by Parliament through the Electric Lighting Orders Confirmation (No. 1) Act 1891 (54 & 55 Vict. c. xlix).[1]

The power station was built north of the town off Ripon Road Harrogate (54°00’03”N 01°33’17”W); it began to supply electricity on 14 April 1897. The site was adjacent to the Oak Beck which provided make-up water to the station's spray cooling pond.[2]

The Central Electricity Board built the first stages of the National Grid between 1927 and 1933. Harrogate power station were connected to the 132 kV electricity grid.[3] In 1935 Ripon ceded its electricity supply rights to the Harrogate electricity undertaking.[4]

The British electricity supply industry was nationalised in 1948 under the provisions of the Electricity Act 1947 (10 & 11 Geo. 6 c. 54).[5] The Harrogate electricity undertaking was abolished, ownership of Harrogate power station was vested in the British Electricity Authority, and subsequently the Central Electricity Authority and the Central Electricity Generating Board (CEGB).[6] At the same time the electricity distribution and sales responsibilities of the Harrogate undertaking were transferred to the North Eastern Electricity Board (NEEB).

Following nationalisation Harrogate power station became part of the Harrogate electricity supply district, covering an area of 192,084 acres (77,734 ha).[2]

Harrogate power station was closed in 1960.[7]

Equipment specification

edit

Plant in 1898

edit

The plant in 1898 comprised Belliss and McLaren engines coupled directly to Ferranti and Siemens alternators. The capacity of the generating plant was 575 kW and the maximum load was 156 kW.[8]

Plant in 1923

edit

By 1923 the plant at Harrogate comprised boilers delivering a total of 50,000 lb/h (6.3 kg/s) of steam to:[9]

  • 1 × 300 kW turbo-alternator generating alternating current (AC)
  • 1 × 1,000 kW turbo-alternator generating AC
  • 1 × 1,200 kW turbo-alternator generating AC
  • 1 × 1,250 kW turbo-alternator generating AC

In addition there was one 400 kW oil-fired engine driven alternator generating AC

The total generating capacity was 4,150 kW.

Plant in 1954

edit

By 1954 the plant comprised:[2]

  • Boilers:
    • 2 × Holdsworth 12,000 lb/hr (1.51 kg/s), steam conditions were 180 psi at 600 °F (12.4 bar and 316 °C)
    • 2 × Yarrow 50,000 lb/h (6.3 kg/s), steam conditions were 300 psi and 700 °F (20.7 bar and 371 °C), steam was supplied to:
  • Generators (turbo-alternators):
    • 1 × 1.875 MW Brush
    • 1 × 4.5 MW F & C, 3.66 kV
    • 1 × 8.0 MW Parsons, 11 kV
    • 1 × 1.5 MW F & C, 3.46 kV

The total installed generating capacity was 15.875 MW.

Water cooling was by spray coolers and pond, the circulation capacity was 0.95 million gallons per hour (1.2 m3/s).[2]

Operations

edit

Operating data 1921–23

edit

The electricity supply data for the period 1921–23 was:[9]

Harrogate power station supply data 1921–23
Electricity Use Units Year
1921 1922 1923
Lighting and domestic MWh 1,781 1,954 2,419
Public lighting MWh 95 95 107
Traction MWh 0 0 0
Power MWh 482 498 473
Bulk supply MWh 0 0 0
Total use MWh 2,359 2,547 2,999

Electricity Loads on the system were:

Year 1921 1922 1923
Maximum load kW 1,596 1,760 1,785
Total connections kW 5,580 6,057 6,782
Load factor Per cent 22.5 22.2 24.0

Revenue from the sale of current (in 1923) was £52,102; the surplus of revenue over expenses was £29,420.[9]

Operating data 1946

edit

In 1946 Harrogate power station supplied 9,501 MWh of electricity; the maximum output load was 9,076 kW.[10]

Operating data 1954–60

edit

Operating data for the period 1954–58 was:[2]

Harrogate power station operating data, 1954–58
Year Running hours, Max output capacity MW Electricity supplied MWh Thermal efficiency per cent
1954 596 8 2,816 12.42
1955 1008 8 4,887 13.18
1956 718 8 3,454 14.06
1957 693 8 3,047 13.45
1958 941 8 4,262 13.98

Harrogate Electricity District

edit

Following nationalisation in 1948 Harrogate power station became part of the Harrogate electricity supply district, covering 192,084 acres (77,734 ha). The number of consumers and electricity sold in the Harrogate district was:[2]

Year 1956 1957 1958
Number of consumers 31,093 32,669 33,475
Electricity sold MWh 88,589 95,433 104,690

In 1958 the number of units sold to categories of consumers was:[2]

Type of consumer No. of consumers Electricity sold MWh
Residential 27,459 60,868
Commercial 4,017 21,939
Industrial 465 14,262
Farms 1,508 6.388
Traction 0 0
Public lighting 26 1,133
Total 33,475 104,690

See also

edit

References

edit
  1. ^ "Local Acts 1891". www.legislation.gov.uk. Retrieved 4 January 2022.
  2. ^ a b c d e f g Garrett, Frederick C., ed. (1959). Garcke's Manual of Electricity Supply vol. 56. London: Electrical Press. pp. A-61, A-122, B-170.
  3. ^ "Open Infrastructure Map". openinframap.org. Retrieved 4 January 2022.
  4. ^ Hannah, Leslie (1979). Electricity before Nationalisation. London: Macmillan. pp. 247–8. ISBN 0333220862.
  5. ^ "Electricity Act 1947". www.legislation.gov.uk. Retrieved 4 January 2022.
  6. ^ Electricity Council (1987). Electricity supply in the United Kingdom: a Chronology. London: Electricity Council. pp. 45, 60–61. ISBN 085188105X.
  7. ^ Harrogate power station is listed in Garcke’s Manual 1959 but not in the CEGB Annual Report 1961
  8. ^ Garcke, Emile (1898). Manual of Electrical Undertakings 1898-99 vol. 3. London: P. S. King and Son. p. 203.
  9. ^ a b c Electricity Commissioners (1925). Electricity Supply – 1920–23. London: HMSO. pp. 38–41, 284–89.
  10. ^ Electricity Commissioners, Generation of Electricity in Great Britain year ended 31 December 1946 HMSO 1947 p.9